A breaker trips for two different reasons, and how fast it trips tells you which one.

The whole flat went dark at once · The lights dimmed, then everything stopped · It happens every time the air conditioning starts · The handle will not stay up, it clicks straight back down · One room is out and the rest is fine · Every handle is up but nothing has power · It tripped with nothing new running · It tripped the moment I plugged something in · I reset it and it tripped again five minutes later
FreeLook at a neighbour's window before you touch anything
FreeSwitch off the heavy loads, then reset once
FreeBring the circuits back one at a time to find the culprit
Easy · 15 min · Every step on this page is free, and the first one happens at the window

A room at night with its window open onto the building opposite, where several windows are lit; below it in the hallway, the electricity meter with a small screen beside the open consumer unit — a main switch, a row of five breakers and an RCD with a yellow test button; right, one breaker in section — a red handle, a pair of contacts, a curved bimetal strip, a trip coil and the latch that holds it all closed

diagnose
What failed
—
Where
—
State
—
Next
—
what to touch fault correct Click the window, the meter or a breaker

Two trip mechanisms in one plastic case

Open a domestic breaker and you find a switch, a spring, and two entirely separate devices whose only job is to let that spring go. The first is a bimetal strip: two metals bonded together with different expansion rates, heated by the current passing through them. Overload it and the strip bends, and after seconds or minutes it pushes the latch aside. Slow, and proportional — a 30 A breaker on a 45 A load will trip in a minute or two, on a 90 A load in a few seconds.

The second is a small solenoid with the current-carrying wire wound into it. At five to ten times rated current the magnetic field is strong enough to yank a plunger and release the same latch directly, in milliseconds. It does not wait for anything to heat up, because a short circuit is not a slow problem — it is hundreds of amps and it will destroy the cable in seconds.

Which means the diagnosis is already written in the behaviour. A breaker you can push up, that holds for a while and then drops, is being tripped by heat: an overload. Something is drawing more than the circuit is rated for, and the strip is doing exactly what it should. A breaker that clicks straight back down the instant you push it is being tripped by magnetism: a fault. Live to neutral, or live to earth, is finding a path it should not have. Reset is not the answer to either one; it is only the measurement.

Why the reset order matters as much as the reset

Here is the mistake almost everyone makes. They push the handle up with every appliance still switched on, it holds for a second and drops again, and they conclude the breaker is broken. It is not — they have just asked it to close into a live load. Motors draw five to seven times their running current for the first fraction of a second: an air conditioner, a fridge compressor, a washing machine, a pump. That inrush is enough to fire the magnetic trip on a circuit that is nowhere near overloaded once everything is running.

So the order is: switch off the heavy loads at the appliance, then reset, then bring them back one at a time. And if it drops again with everything off, stop after the second attempt. Every reset into a fault draws an arc across the contacts, and an arc pits the silver. Do that twenty times and the breaker will genuinely fail — it will feel loose, or it will hold but run warm, and then you have turned a free diagnosis into a part you have to buy.

The third device, and why "nothing was overloaded" is not a contradiction

An RCD — the wider device with the test button — does not measure current at all. It measures the difference between the current going out on the live and coming back on the neutral. In a healthy circuit those are identical and the difference is zero. If 30 milliamps is escaping to earth — through a damaged cable, a damp socket, a failing heating element, or a person — the difference is 30 milliamps and it trips in under a second. Thirty milliamps is not an overload. It is a tenth of a light bulb. So a house where nothing is drawing too much current can still trip its RCD all day, and it is not being oversensitive: something is leaking.

That is why the two faults need different searches. For an overload you are looking for what is running; for a leakage trip you are looking for what is connected, and often for one thing that is damp — a kettle that boiled over, an outdoor socket after rain, a washing machine whose door seal has been leaking into the motor for a year. Unplug everything, reset, then bring them back one at a time. The one that trips it is the one that leaks, and it will trip it every time, which is exactly what you want from a fault.

Three rules, and the third is how old flats burn down. Dry hands, dry floor. The handle is insulated plastic, but the panel around it is not, and a consumer unit in a damp hallway deserves a moment's thought before you put a hand near it. Two attempts, then stop. A breaker that will not hold is telling you there is a real fault downstream, and repeating the reset does not clear a fault, it only wears the contacts. Never wire a breaker shut, and never replace it with a bigger one. A blown fuse replaced with foil, or a handle tied up with wire, defeats the only device standing between a faulty appliance and the cable inside your wall. That is not a shortcut, it is a fire waiting for a reason.

Faults next to this one